Skip to content

PGsT-MU

Measuring transducer up to 1500 V DC measuring voltage for direct current power installations up to 1000 V (CAT III)

Description

Measuring transducer up to 1500 V DC measuring voltage for direct current power installations up to 1000 V (CAT III)

Application
The measuring transducer PGsT-MU is used for the transformation and isolation of a DC power into an impressed direct current and direct voltage signal. An integrated limit monitoring serves for monitoring the input signal.

Function
The parameters to be measured are transmitted to the microcontroller via internal voltage dividers or shunts. The instantaneous values are then multiplied and formed as the mean value of a direct voltage matching the DC power in a subsequent integration stage. The galvanic isolation is realized using an optocoupler. An downstream amplifier supplies the impressed direct current and direct voltage signals. Both outputs are no-load proof and short-circuit proof. Connecting the two outputs is not permissible. The limit value may be adjusted within a range of 0-120 % of the input signal. An auxiliary voltage is required.

Downloads
PDF-general description
PDF-product description
PDF-operating manual

Enquiry